(1)
In general
Subject to paragraphs (2) through (5), each walk-in cooler or walk-in freezer manufactured on or after January 1, 2009, shall—
(A)
have automatic door closers that firmly close all walk-in doors that have been closed to within 1 inch of full closure, except that this subparagraph shall not apply to doors wider than 3 feet 9 inches or taller than 7 feet;
(B)
have strip doors, spring hinged doors, or other method of minimizing infiltration when doors are open;
(C)
contain wall, ceiling, and door insulation of at least R–25 for coolers and R–32 for freezers, except that this subparagraph shall not apply to glazed portions of doors nor to structural members;
(D)
contain floor insulation of at least R–28 for freezers;
(E)
for evaporator fan motors of under 1 horsepower and less than 460 volts, use—
(i)
electronically commutated motors (brushless direct current motors); or
(F)
for condenser fan motors of under 1 horsepower, use—
(i)
electronically commutated motors;
(ii)
permanent split capacitor-type motors; or
(iii)
3-phase motors; and
(G)
for all interior lights, use light sources with an efficacy of 40 lumens per watt or more, including ballast losses (if any), except that light sources with an efficacy of 40 lumens per watt or less, including ballast losses (if any), may be used in conjunction with a timer or device that turns off the lights within 15 minutes of when the walk-in cooler or walk-in freezer is not occupied by people.
(2)
Electronically commutated motors
(A)
In general
The requirements of paragraph (1)(E)(i) for electronically commutated motors shall take effect January 1, 2009, unless, prior to that date, the Secretary determines that such motors are only available from 1 manufacturer.
(B)
Other types of motors
In carrying out paragraph (1)(E)(i) and subparagraph (A), the Secretary may allow other types of motors if the Secretary determines that, on average, those other motors use no more energy in evaporator fan applications than electronically commutated motors.
(C)
Maximum energy consumption level
The Secretary shall establish the maximum energy consumption level under subparagraph (B) not later than January 1, 2010.
(3)
Additional specifications
Each walk-in cooler or walk-in freezer with transparent reach-in doors manufactured on or after January 1, 2009, shall also meet the following specifications:
(A)
Transparent reach-in doors for walk-in freezers and windows in walk-in freezer doors shall be of triple-pane glass with either heat-reflective treated glass or gas fill.
(B)
Transparent reach-in doors for walk-in coolers and windows in walk-in cooler doors shall be—
(i)
double-pane glass with heat-reflective treated glass and gas fill; or
(ii)
triple-pane glass with either heat-reflective treated glass or gas fill.
(C)
If the appliance has an antisweat heater without antisweat heat controls, the appliance shall have a total door rail, glass, and frame heater power draw of not more than 7.1 watts per square foot of door opening (for freezers) and 3.0 watts per square foot of door opening (for coolers).
(D)
If the appliance has an antisweat heater with antisweat heat controls, and the total door rail, glass, and frame heater power draw is more than 7.1 watts per square foot of door opening (for freezers) and 3.0 watts per square foot of door opening (for coolers), the antisweat heat controls shall reduce the energy use of the antisweat heater in a quantity corresponding to the relative humidity in the air outside the door or to the condensation on the inner glass pane.